Technical specifications
A.6 CPU 1214C
Technical data
Switching delay (Qa.0 to Qa.3)
Switching delay (Qa.4 to Qb.1)
Maximum relay switching frequency
Pulse Train Output rate
Lifetime mechanical (no load)
Lifetime contacts at rated load
Behavior on RUN to STOP
Number of outputs on simultaneously •
Cable length (meters)
Relay group-to-group isolation separates line voltage from SELV/PELV and separates different phases up to 250 V AC
1
line to ground.
For CPU models with relay outputs, you must install a digital signal board (SB) to use the pulse outputs.
2
Depending on your pulse receiver and cable, an additional load resistor (at least 10% of rated current) may improve
3
pulse signal quality and noise immunity.
1402
CPU 1214C AC/DC/Relay
and DC/DC/Relay
10 ms max.
10 ms max.
1 Hz
Not recommended
2
10,000,000 open/close cycles
100,000 open/close cycles
Last value or substitute value (default value 0)
5 (no adjacent points) at 60 °C horizontal or 50 °C vertical
10 at 55 °C horizontal or 45 °C vertical
•
500 m shielded, 150 m unshielded
CPU 1214C
DC/DC/DC
1.0 μs max., off to on
3.0 μs max., on to off
5 μs max., off to on
20 μs max., on to off
--
100 kHz (Qa.0 to Qa.3)
20 kHz (Qa.4 to Qb.1)
--
--
S7-1200 Programmable controller
System Manual, V4.2, 09/2016, A5E02486680-AK
, 2 Hz min.
3
3