Z1: NC/PLC interface signals
19.3 Continuous-path mode, exact stop and LookAhead (B1)
DB31, ...
DBX102.5/6
Position measuring system1/2 activated
Edge evaluation: No
Signal state 1
The position measuring system is in the "active" or "passive" state. Monitoring and updating the
position measuring system is activated.
Signal state 0
The position measuring system is in the "Park" state. Monitoring and updating the position measuring
system is deactivated.
"Parked" status is entered if:
● for the axis/spindle, the NC/PLC interfaces signals for the configured position measuring systems
● "Parking the passive measuring system" is active for the measuring system:
19.3
Continuous-path mode, exact stop and LookAhead (B1)
19.3.1
Signals from channel (DB21, ...)
DB21, ...
DBX36.3
All axes stationary
Edge evaluation: no
Signal state 1 or
All axes assigned to the channel are stationary with interpolator end.
edge change
No other traversing movements are active.
0 → 1
1592
Signal(s) updated: Cyclically
and control enable are reset:
–
DB31, ... DBX1.5 (position measuring system 1) = 0
–
DB31, ... DBX1.6 (position measuring system 2) = 0
–
DB31, ... DBX2.1 (controller enable) = 0
or
–
MD31046 $MA_ENC_PASSIVE_PARKING[<n>] = 1
with <n> = 0 (position measuring system 1) or 1 (position measuring system 2)
and the NC/PLC interface signal for the position measuring system was reset to "0" by the user:
–
DB31, ... DBX1.5 (position measuring system 1) = 0
or
–
DB31, ... DBX1.6 (position measuring system 2) = 0
Signal(s) updated: cyclic
Function Manual, 01/2015, 6FC5397-0BP40-5BA2
Basic Functions