Control Output Cycle Unit Selection Function - Mitsubishi Electric NZ2GF2B-60TCTT4 User Manual

Cc-link ie field network temperature control module
Table of Contents

Advertisement

8.3.6

Control output cycle unit selection function

The unit of the control output cycle can be selected from 1s or 0.1s using this function.
When the control output cycle is set in 0.1s, control can be more attentive.
The control output cycle is the ON/OFF cycle of transistor output for the temperature control function.
The cycle can be set in the following parameter setting screen.
Control mode
Standard control
Heating-cooling control
(1) Setting method
1.
Set "Method selection" to "Param write (Station parameter)".
"CC IE Field Configuration" windowSelect the temperature control module from "List of
stations"[CC IE Field Configuration][Online][Parameter Processing of Slave Station]
2.
Set "Control output cycle unit switching setting".
An error (error code: 000EH) occurs right after changing this setting. To recover from the error status, turn on and off Set
value backup instruction (RY15) and register the setting after the change to the temperature control module.
158
CH Control output cycle setting
CH Heating control output cycle setting
CH Cooling control output cycle setting
Standard
Item
Heating-cooling

Advertisement

Table of Contents
loading