hit counter script

Mitsubishi Electric NZ2GF2B-60TCTT4 User Manual page 192

Cc-link ie field network temperature control module
Table of Contents

Advertisement

(d) The temperature process value (PV) is not within the temperature measurement
range.
The self-tuning is not executed. CH Self-tuning disable status (b8 of RWr14 to RWr17) turns 1 (ON).
(e) The value set in CH Output variation limiter setting (address: 107H, 137H, 167H,
197H) is not 0.
The self-tuning is not executed. CH Self-tuning disable status (b8 of RWr14 to RWr17) turns 1 (ON).
If the setting value is not 0, refer to the following.
Page 323, Appendix 3 (11)
(f) CH AUTO/MAN mode shift (address: 113H, 143H, 173H, 1A3H) is set to MAN (1).
The self-tuning is not executed. CH Self-tuning disable status (b8 of RWr14 to RWr17) turns 1 (ON).
If the setting is MAN (1), refer to the following.
Page 332, Appendix 3 (22)
(g) Values other than 0 (0.0%) have been set for the setting change rate limiter.
If the values other than 0 (0.0%) have been set to the following remote buffer memory areas, self-tuning is not
executed. CH Self-tuning disable status (b8 of RWr14 to RWr17) turns 1 (ON).
Remote buffer memory area name
CH Setting change rate limiter/Setting change rate limiter (temperature rise)
CH Setting change rate limiter (temperature drop)
If the setting value is other than 0 (0.0%), refer to the following.
Page 325, Appendix 3 (13)
(h) The heating-cooling control has been selected for the control mode.
The self-tuning is not executed.
If the heating-cooling control has been selected, refer to the following.
Page 311, Appendix 3 (3)
(7) Discontinuation of self-tuning
The following operation during self-tuning discontinues the self-tuning operation.
• The setting in CH Self-tuning setting (address: 2C0H to 2C3H) has been changed to Do Not run the ST
(0).
The self-tuning operation in process is discontinued and self-tuning is not performed anymore after that. (An error
does not occur.)
Whether self-tuning is being executed can be checked in CH Auto tuning status (RX20 to RX23). (Page
291, Appendix 1.1 (12))
190
Remote buffer memory address
CH1
CH2
108H
138H
1C8H
1CDH
CH3
CH4
168H
198H
1D2H
1D7H

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nz2gf2b-60tcrt4

Table of Contents