hit counter script

Chapter 9 Programming; Precautions For Programming - Mitsubishi Electric NZ2GF2B-60TCTT4 User Manual

Cc-link ie field network temperature control module
Table of Contents

Advertisement

CHAPTER 9
This chapter describes the programming of a temperature control module.
9.1

Precautions for Programming

This section describes precautions to create CC-Link IE Field Network programs.
(1) Cyclic transmission program
For a cyclic transmission program, interlock with the following link special relay (SB) and link special register
(SW).
• Own station data link status (master station) (SB0049)
• Data link status (each station) (SW00B0 to SW00B7)
For the link special relay (SB) and link special register (SW), refer to the following.
 User's manual for the master/local module used
Interlock example
Ex.
(2) Transient transmission program
For a transient transmission program, interlock with the following link special relay (SB) and link special register
(SW).
• Own station baton pass status (master station) (SB0047)
• Baton pass status (each station) (SW00A0 to SW00A7)
For the link special relay (SB) and link special register (SW), refer to the following.
 User's manual for the master/local module used
Interlock example
Ex.
Start-up contact
232
PROGRAMMING
Communication program with station No.1
Communication program with station No.2
Dedicated instruction to station No.1

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nz2gf2b-60tcrt4

Table of Contents