(b) List of error codes (0160H to 3FFFH, D529H, D52BH)
Error code
Classification
(hexadecimal)
Remote buffer
0160H
Minor error
memory access
error
Cyclic data update
0930H
Moderate error
watch time setting
outside the range
Station number
0940H
Minor error
switch changed
error
Clock data outside
0950H
Moderate error
the range
Network No.
0960H
Major error
changed through
the network
Station No.
0970H
Major error
changed through
the network
Communication
D529H
Major error
error 1
Communication
D52BH
Major error
error 2
*1
The error details written here are for the case when Error history is A06H to A09H (for Error history 1 (address: A00H to
A0FH)). The following information of when an error has occurred are stored in this area.
• Error occurrence address
• Process value (PV)
• Manipulated value (MV)
• Set value (SV)
For details on Error history, refer to the following.
Page 363, Appendix 3 (69)
When multiple errors have occurred, only the latest error code is stored in Latest error code (RWr0) or Latest warning code
(RWr2).
The errors that occurred in the past can be checked with the error history of the engineering tool.
For the error history, refer to the following.
• Checking with the command execution of slave station (Page 267, Section 11.1 (1))
• Error history (address: A00H to FFFH) (Page 363, Appendix 3 (69))
Description and
Error name
cause
A buffer memory
area other than the
remote buffer
memory areas has
been accessed using
the REMFR/REMTO
instruction.
The value set in
Cyclic data update
watch time (address:
7H) is outside the
range of 0 to 20.
The station number
setting switch has
been changed while
the module power is
on.
The clock data
acquired from the
CPU module is
invalid.
Invalid change of a
network number has
been detected.
Invalid change of a
station number has
been detected.
A communication
error has occurred.
CHAPTER 11 TROUBLESHOOTING
*1
Error details
0 is stored in Error occurrence
Correct the setting data of the
address, Process value (PV),
REMFR/REMTO instruction to access the
Manipulated value (MV), and
remote buffer memory.
Set value (SV).
• 0007H is stored in Error
occurrence address.
Set a value within the range of 0 to 20 in
• 0 is stored in Process value
Cyclic data update watch time (address:
(PV), Manipulated value
7H).
(MV), and Set value (SV).
0 is stored in Error occurrence
Set the switch again to the same station
address, Process value (PV),
number that was set while the module
Manipulated value (MV), and
power was on.
Set value (SV).
The possible cause is an affect of noise or
0 is stored in Error occurrence
a hardware failure. If the same error has
address, Process value (PV),
occurred even after measures have been
Manipulated value (MV), and
taken against noise, please consult your
Set value (SV).
local Mitsubishi representative.
The possible cause is an affect of noise or
0 is stored in Error occurrence
a hardware failure. If the same error has
address, Process value (PV),
occurred even after measures have been
Manipulated value (MV), and
taken against noise, please consult your
Set value (SV).
local Mitsubishi representative.
The possible cause is an affect of noise or
0 is stored in Error occurrence
a hardware failure. If the same error has
address, Process value (PV),
occurred even after measures have been
Manipulated value (MV), and
taken against noise, please consult your
Set value (SV).
local Mitsubishi representative.
• The possible cause is malfunction due to
noise. Check the cable distance or
grounding condition of each device and
0 is stored in Error occurrence
take measures against noise.
address, Process value (PV),
• Execute a unit test for the module. If the
Manipulated value (MV), and
same error has occurred, the possible
Set value (SV).
cause is a hardware failure of the
module. Please consult your local
Mitsubishi representative.
Action
11