Remark
For the following mode and channel, CH Input range (address: 100H, 130H, 160H, 190H) cannot be set to 201 to 205. If
these values are set, a write data error (error code: 0004H) occurs.
Temperature input mode
Temperature control mode
(b) Setting range of NZ2GF2B-60TCRT4
Set CH Input range (address: 100H, 130H, 160H, 190H) according to the platinum resistance thermometer
type.
Temperature
Platinum resistance
measurement
thermometer type
range
-200.0 to 600.0
-200.0 to 200.0
Pt100
-200.0 to 850.0
-300 to 1100
-300.0 to 300.0
-200.0 to 500.0
-200.0 to 200.0
JPt100
-200.0 to 640.0
-300 to 900
-300.0 to 300.0
Input from other analog
0 to 4000
*2
modules (0 to 4000)
Input from other analog
0 to 12000
*2
modules (0 to 12000)
Input from other analog
0 to 16000
*2
modules (0 to 16000)
Input from other analog
0 to 20000
*2
modules (0 to 20000)
Input from other analog
0 to 32000
*2
modules (0 to 32000)
*1
When the input range is changed, the set values in some remote buffer memory areas are initialized automatically and
return to the default value (0). (Page 316, Appendix 3 (5) (d))
*2
Same as the NZ2GF2B-60TCTT4.
Remark
For the following mode and channel, CH Input range (address: 100H, 130H, 160H, 190H) cannot be set to 201 to 205. If
these values are set, a write data error (error code: 0004H) occurs.
Temperature input mode
Temperature control mode
Mode
Heating-cooling control (normal mode)
Mix control (normal mode)
Celsius ()
CH Input range
/Fahrenheit
Resolution
(address: 100H,
()/digit
130H, 160H, 190H)
0.1
7 (Default value)
0.1
8
0.1
54
1
141
0.1
143
0.1
5
0.1
6
0.1
53
1
140
0.1
142
digit
1
201
digit
1
202
digit
1
203
digit
1
204
digit
1
205
Mode
Heating-cooling control (normal mode)
Mix control (normal mode)
Corresponding channel
CH1 to CH4
CH3, CH4
CH2
Auto-setting at input range change
CH Upper limit setting
CH Lower limit setting
limiter, CH Process
limiter, CH Process
alarm upper lower limit
alarm lower lower limit
value, CH Process
value, CH Process
alarm upper upper limit
alarm lower upper limit
value
6000
-2000
2000
-2000
8500
-2000
1100
-300
3000
-3000
5000
-2000
2000
-2000
6400
-2000
900
-300
3000
-3000
4000
0
12000
0
16000
0
20000
0
32000
0
Corresponding channel
CH1 to CH4
CH3, CH4
CH2
APPENDICES