hit counter script

Mitsubishi Electric NZ2GF2B-60TCTT4 User Manual page 293

Cc-link ie field network temperature control module
Table of Contents

Advertisement

(12)CH Auto tuning status (RX20 to RX23)
This signal turns on when auto tuning of each channel is executed with the program or when the temperature
control module executes self-tuning.
Channel
Standard control
CH1
RX20
CH2
RX21
CH3
RX22
CH4
RX23
*1
Available only under the heating-cooling control (expanded mode). For details on the expanded mode, refer to the
following. (Page 147, Section 8.3.1 (3))
*2
Available only under the mix control (expanded mode). For details on the expanded mode, refer to the following.
(Page 147, Section 8.3.1 (3))
(a) Execution of auto tuning
To execute auto tuning, turn on CH Auto tuning instruction (RY20 to RY23).
This signal is on during auto tuning, and automatically turns off at the completion of the auto tuning.
CH□ Auto tuning instruction
CH□ Auto tuning status
For details on the auto tuning function, refer to the following.
Page 159, Section 8.3.7
(b) Self-tuning
This signal turns on when self-tuning starts. The signal automatically turns off at the completion of the self-
tuning.
Set self-tuning timings in CH Self-tuning setting (address: 2C0H to 2C3H). (Page 356, Appendix 3 (58))
Self-tuning can be executed only in the standard control.
For details on the self-tuning function, refer to the following.
Page 184, Section 8.3.15
Auto tuning status
Heating-cooling
Mix control
control
RX20
RX20
*2
RX21
RX21
*1
RX22
RX22
*1
RX23
RX23
ON
OFF
(RY20 to RY23)
OFF
(RX20 to RX23)
Controlled by the program
Controlled by the temperature control module
Standard
Heating-cooling
ON/OFF status
ON: During auto tuning/self-tuning
OFF: The auto tuning/self-tuning has not been executed or is completed.
ON
During auto tuning
APPENDICES