Mitsubishi Electric NZ2GF2B-60TCTT4 User Manual page 288

Cc-link ie field network temperature control module
Table of Contents

Advertisement

(4) Remote READY (RXB)
This signal is used as an interlock condition when the master station reads/writes data from/to the remote register
or remote buffer memory areas of the temperature control module.
The signal turns on when the module power supply is turned on.
When Error flag (RXA) turns on, the signal turns off.
(5) During operation setting change completion flag (RX10)
If parameters are changed during operation of the temperature control module and During operation setting
change instruction (RY10) is turned on, this signal turns on at the normal completion of the setting change.
The signal turns off when During operation setting change instruction (RY10) is turned off.
Remote buffer memory
During operation setting
change instruction (RY10)
During operation setting
change completion flag
Sampling cycle (500ms)
Reflection of a setting value
For parameters that can be changed during operation, refer to the following.
• Lists of Remote Buffer Memory Areas (Page 49, Section 3.7)
286
Common
Controlled by the program
Controlled by the temperature control module
Setting value A
OFF
OFF
(RX10)
500ms
Setting value A
Setting value B
ON
500ms
500ms
Setting value B
Common
OFF
ON
OFF
500ms