Mitsubishi Electric NZ2GF2B-60TCTT4 User Manual page 276

Cc-link ie field network temperature control module
Table of Contents

Advertisement

Error
code
Classification
(hexadecimal)
*4
Moderate error
001H
*4
Moderate error
002H
*1
The error details written here are for the case when Error history is A06H to A09H (for Error history 1 (address: A00H to
A0FH)). The following information of when an error has occurred are stored in this area.
• Error occurrence address
• Process value (PV)
• Manipulated value (MV)
• Set value (SV)
For details on Error history, refer to the following.
Page 363, Appendix 3 (69)
*2
For the area where data can be written only during the module stop, refer to Lists of Remote Buffer Memory Areas.
Page 49, Section 3.7
*3
If the following values are stored in Error occurrence address, 0 is stored in Process value (PV), Manipulated value
(MV), and Set value (SV) of Error history.
0001H, 0007H, 0080H, 0081H, 01E0H to 01EAH, 1000H
*4
 represents the channel number where an error has occurred.
When multiple errors have occurred, only the latest error code is stored in Latest error code (RWr0) or Latest warning code
(RWr2).
The errors that occurred in the past can be checked with the error history of the engineering tool.
For the error history, refer to the following.
• Checking with the command execution of slave station (Page 267, Section 11.1 (1))
• Error history  (address: A00H to FFFH) (Page 363, Appendix 3 (69))
274
Operation at error
Cause
occurrence
When either of
CH Operation
request flag (RY11
The operating status
to RY14) or CH
remains same as
Stop request flag
before the error
(RY18 to RY1B)
occurrence.
was on, the other
signal was also
turned on.
The value written
• The data written is
to CH
retained.
Temperature
• The control is
process value for
performed with the
input with another
upper/lower limit
analog module
value within the
(PV) (RWw0 to
setting range.
RWw3) is invalid.
*1
Error details
• The process value of the
error channel is stored in
Process value (PV).
• The manipulated value of
Turn off CH Operation request flag (RY11
the error channel is stored
to RY14) or CH Stop request flag (RY18
in Manipulated value (MV).
to RY1B) of the error channel.
• The set value of the error
channel is stored in Set
value (SV).
• The process value of the
error channel is stored in
Process value (PV).
Set the value within the setting range to
• The manipulated value of
CH Temperature process value for input
the error channel is stored
with another analog module (PV) (RWw0 to
in Manipulated value (MV).
RWw3) of the error channel.
• The set value of the error
channel is stored in Set
value (SV).
Action