Mitsubishi Electric NZ2GF2B-60TCTT4 User Manual page 274

Cc-link ie field network temperature control module
Table of Contents

Advertisement

Error
code
Classification
(hexadecimal)
0004H
Moderate error
0005H
Moderate error
0006H
Moderate error
0007H
Moderate error
272
Operation at error
Cause
occurrence
• The data written is
retained.
• If temperature,
time, or
percentage
Data out of the
settings exceed
setting range is
upper limit
being written.
value/lower limit
value, the control
is performed with
the upper limit
value/lower limit
value.
• The data written is
The setting of the
retained.
upper/lower limit
• The control is
output limiter or the
performed with the
upper/lower limit
upper/lower limit
setting limiter is
value within the
invalid.
setting range.
• The data written is
ignored.
• The setting value
cannot be
The setting value is
changed until the
being changed
error is cleared.
while Default
• The content of
setting registration
Latest error code
instruction (RY16)
(RWr0) does not
is on.
change even if
another write error
occurs.
• The data written is
retained.
• The control is
performed with the
data of before the
setting.
• If both the offset
value and gain
The sensor two-
value are within
point correction
the input range
setting is invalid.
and the offset
value is greater
than or equal to
the gain value, the
gain value address
is stored in Error
occurrence
address.
*1
Error details
• The address of remote
buffer memory area where
an error has occurred is
stored in Error occurrence
*3
address.
• The process value of the
error channel is stored in
Set the data within the setting range.
Process value (PV).
• The manipulated value of
the error channel is stored
in Manipulated value (MV).
• The set value of the error
channel is stored in Set
value (SV).
• The address of remote
buffer memory area where
an error has occurred is
stored in Error occurrence
*3
address.
• The process value of the
Set the value where the upper limit value is
error channel is stored in
greater than the lower limit value.
Process value (PV).
• The manipulated value of
the error channel is stored
in Manipulated value (MV).
• The set value of the error
channel is stored in Set
value (SV).
• The address of remote
buffer memory area where
an error has occurred is
stored in Error occurrence
*3
address.
• The process value of the
Turn on and off Error clear request flag
error channel is stored in
(RYA) and change the setting value.
Process value (PV).
• The manipulated value of
the error channel is stored
in Manipulated value (MV).
• The set value of the error
channel is stored in Set
value (SV).
• The address of remote
buffer memory area where
an error has occurred is
stored in Error occurrence
*3
address.
• The process value of the
error channel is stored in
Process value (PV).
• The manipulated value of
the error channel is stored
in Manipulated value (MV).
• The set value of the error
channel is stored in Set
value (SV).
Action
• Enter the temperature within the input
range.
• Set the values so that the sensor two-
point correction offset value (measured
value) is smaller than the sensor two-
point correction gain value (measured
value) and the sensor two-point
correction offset value (corrected value)
is smaller than the sensor two-point
correction gain value (corrected value).