(8) CH Integral time (I) setting (address: 103H, 133H, 163H, 193H)
Set integral time (I) to perform PID control.
(a) Setting range
The setting range is 0 to 3600 (0 to 3600s).
(b) In the P control or PD control
Set this setting to 0.
For details on control methods, refer to the following.
Page 149, Section 8.3.3
(c) Enabling the setting
Enable the setting contents by either of the following.
• Turning off and on Initial data setting request flag (RY9) while the operations of all channels are stopped
• Turning off and on During operation setting change instruction (RY10)
(d) Default value
The default values are set to 240 (240s) in all channels.
(9) CH Derivative time (D) setting (address: 104H, 134H, 164H, 194H)
Set derivative time (D) to perform PID control.
(a) Setting range
The setting range is 0 to 3600 (0 to 3600s).
(b) In the P control or PI control
Set this setting to 0.
For details on control methods, refer to the following.
Page 149, Section 8.3.3
(c) Enabling the setting
Enable the setting contents by either of the following.
• Turning off and on Initial data setting request flag (RY9) while the operations of all channels are stopped
• Turning off and on During operation setting change instruction (RY10)
(d) Default value
The default values are set to 60 (60s) in all channels.