(7) CH Stop request flag (RY18 to RY1B)
Turn on this signal to stop operation in a channel.
• If this signal is turned on during the operation of temperature control module, operation is stopped for the
corresponding channel and CH Operation monitor (RX11 to RX14) turns off. (The operation is stopped
according to the setting of CH Stop mode setting (address: 118H, 148H, 178H, 1A8H).) Check that CH
Operation monitor (RX11 to RX14) is off, and turn off the signal.
Controlled by the program
Controlled by the temperature control module
CH□ Stop request flag
(RY18 to RY1B)
Module status
CH□ Operation monitor
(RX11 to RX14)
• If the signal is turned on during the temperature control module stop, the module remains stopped (CH
Operation monitor (RX11 to RX14) remains off). An error or an alarm is not output.
• If the signal is turned on while CH Operation request flag (RY11 to RY14) is on, an error occurs (error
code: 001H).
Controlled by the program
Controlled by the temperature control module
CH□ Operation request flag
(RY11 to RY14)
Module status
CH□ Operation monitor
(RX11 to RX14)
CH□ Stop request flag
(RY18 to RY1B)
Latest error code (RWr0)
298
ON
OFF
Operating
ON
ON
OFF
Operation shift
Operating
OFF
OFF
0000H
Common
OFF
Stop
OFF
Stop
processing
ON
ON
001□H