(d) Upper lower limit deviation alert
When one of the following conditions is satisfied, the system is put in an alert status.
• Deviation (E)  Alert set value
• Deviation (E)  -(Alert set value)
Temperature process value (PV)
*1
Set value (SV)
Deviation (E) (= Temperature process value (PV) - Set value (SV)
Alert set value
0
- (Alert set value)
Alert status
*1
Depending on the alert mode, this value becomes "set value (SV) monitor" or "set value (SV) setting". (Page 170,
Section 8.3.11 (2) (a))
(e) Within-range alert
When the following condition is satisfied, the system is put in an alert status.
• -(Alert set value)  Deviation (E)  Alert set value
Temperature process value (PV)
*1
Set value (SV)
Deviation (E) (= Temperature process value (PV) - Set value (SV)
Alert set value
0
- (Alert set value)
Alert status
*1
Depending on the alert mode, this value becomes "set value (SV) monitor" or "set value (SV) setting". (Page 170,
Section 8.3.11 (2) (a))