(f) Enabling the setting
To enable the setting, turn off and on Initial data setting request flag (RY9) while the operations of all channels
are stopped.
(6) CH Set value (SV) setting (address: 101H, 131H, 161H, 191H)
Set the target temperature value of PID control.
(a) Setting range
The setting range is identical to the temperature measurement range of the set input range. (Page 313,
Appendix 3 (5))
When a value which is out of the setting range is set, a write data error (error code: 0004H) and the following
situations occur.
• Error flag (RXA) turns on.
• The error code is stored to Latest error code (RWr0).
(b) Setting unit
The value to be set differs depending on the stored value in CH Decimal point position (address: 620H,
621H, 622H, 623H). (Page 362, Appendix 3 (68))
• No decimal place (0): Set a value in 1 ( or digit) unit.
• One decimal place (1): Set a value in 0.1 () unit (tenfold value).
(c) Enabling the setting
Enable the setting contents by either of the following.
• Turning off and on Initial data setting request flag (RY9) while the operations of all channels are stopped
• Turning off and on During operation setting change instruction (RY10)
(d) Default value
The default values are set to 0 in all channels.