Cc-link ie field network temperature control module
Table of Contents

Advertisement

(a) Setting range
• When Control output cycle unit selection setting (address: 1H. b2) is set to the cycle of 1s: 1 to 100 (1s to
100s)
• When Control output cycle unit selection setting (address: 1H. b2) is set to the cycle of 0.1s: 5 to 1000
(0.5s to 100.0s)
For details on the control output cycle unit selection setting function, refer to the following.
Page 158, Section 8.3.6
(b) Two-position control
The setting is ignored.
For details on the two-position control, refer to the following.
Page 149, Section 8.3.3 (1)
(c) Enabling the setting
Enable the setting contents by either of the following.
• Turning off and on Initial data setting request flag (RY9) while the operations of all channels are stopped
• Turning off and on During operation setting change instruction (RY10)
(d) Default value
• When Control output cycle unit selection setting (address: 1H. b2) is set to the cycle of 1s: 30 (30s)
• When Control output cycle unit selection setting (address: 1H. b2) is set to the cycle of 0.1s: 300 (30.0s)
APPENDICES
A
327