Online and diagnostic tools
15.10 Displaying diagnostic events in the CPU
15.10
Displaying diagnostic events in the CPU
Use the diagnostics buffer to review the recent activity in the CPU. The diagnostics buffer is
accessible from "Online & Diagnostics" for an online CPU in the Project tree. It contains the
following entries:
● Diagnostic events
● Changes in the CPU operating mode (transitions to STOP or RUN mode)
You can also use the GET_DIAG instruction (Page 480) to collect the diagnostic information.
1322
The first entry contains the latest event.
Each entry in the diagnostic buffer con-
tains the date and time the event was
logged, and a description.
The maximum number of entries is de-
pendent on the CPU. A maximum of 50
entries is supported.
Only the 10 most recent events in the
diagnostic buffer are stored permanent-
ly. Resetting the CPU to the factory set-
tings resets the diagnostic buffer by
deleting the entries.
S7-1200 Programmable controller
System Manual, V4.2, 09/2016, A5E02486680-AK