■Turning the quick stop command (from controller) or EM2 (Forced stop 2) on/off [G] [B]
In the torque mode and continuous operation to torque control mode, the forced stop deceleration function
cannot be used.
Turn off the quick stop command (from controller) or EM2 (Forced stop 2), then turn off the servo-on
command (from controller) and ready-on command (from controller). If the ready-on command (from
controller) is turned off before the quick stop command (from controller) or EM2 is turned off, Tb [Pr. PC02
Electromagnetic brake sequence output] does not function.
MBR is turned off after the servo motor stops through forced stop deceleration, then the base circuit is turned off after the
base circuit shut-off delay time.
Servo motor speed
Base circuit
(Energy supply to
the servo motor)
Forced stop command
(from controller) or EM2
(Forced stop 2)
MBR
(Electromagnetic
brake interlock)
ALM
(Malfunction)
Electromagnetic brake
Servo-on command
(from controller)
Ready-on command
(from controller)
*1 ON: Electromagnetic brake is not activated
OFF: Electromagnetic brake is activated
*2 The model speed command is a speed command generated in the servo amplifier for forced stop deceleration of the servo motor.
3 BASIC FUNCTION
178
3.18 Electromagnetic brake interlock function
0 r/min
ON
OFF
Disabled
(ON)
Enabled
(OFF)
ON
*1
*1
OFF
ON
(no alarm)
OFF
(alarm)
Release
Activate
ON
OFF
ON
OFF
Model speed command 0
and equal to or less than
*2
zero speed
Tb [Pr. PC02 Electromagnetic
brake sequence output]
Operation delay time
of the electromagnetic
brake