Mitsubishi Electric MELSERVO-J5 User Manual page 209

Ac servo system
Hide thumbs Also See for MELSERVO-J5:
Table of Contents

Advertisement

Timing chart
■When the instantaneous power failure time of the control circuit power supply > [Pr. PF25
SEMI-F47 function - Instantaneous power failure detection time (Instantaneous power failure
tough drive detection time)]
The alarm occurs when the instantaneous power failure time of the control circuit power supply exceeds [Pr. PF25 SEMI-F47
function - Instantaneous power failure detection time (Instantaneous power failure tough drive detection time)]. MTTR turns on
after the instantaneous power failure is detected.
MBR (Electromagnetic brake interlock) turns off when the alarm occurs.
ON
Control circuit
OFF
power supply
Bus voltage
*1
Undervoltage level
ON
ALM
(Malfunction)
OFF
ON
WNG
(Warning)
OFF
ON
MTTR
OFF
MBR
ON
(Electromagnetic
brake interlock)
OFF
ON
Base circuit
OFF
*1 For the undervoltage level, refer to the following table.
Page 210 Behavior
Instantaneous power failure time of control circuit power supply
[Pr. PF25]
4 APPLICABLE FUNCTIONS
4.1 Tough drive function
4
207