hit counter script

Mitsubishi Electric MELSEC-L LD75P User Manual page 129

Positioning module
Hide thumbs Also See for MELSEC-L LD75P:
Table of Contents

Advertisement

(a) Setting range
[Pr.1] setting value
0: mm
1: inch
2: degree
3: pulse
*1
1 to 32767: Set as a decimal
32768 to 65535: Convert into hexadecimal and set
(2) [Pr.12] Software stroke limit upper limit value
Set the upper limit for the machine's movement range during positioning control.
(3) [Pr.13] Software stroke limit lower limit value
Set the lower limit for the machine's movement range during positioning control.
Emergency stop
limit switch
• Generally, the OP is set at the lower limit or upper limit of the stroke limit.
• By setting the upper limit value or lower limit value of the software stroke limit, overrun can be prevented in
the software. However, an emergency stop limit switch must be installed nearby outside the range.
• To invalidate the software stroke limit, set the setting value to "upper limit value = lower limit value". (If it is
within the setting range, the setting value can be anything.)
• When the unit is "degree", the software stroke limit check is invalid during speed control (including speed-
position switching control, position-speed switching control) or during manual control.
(a) Setting range
[Pr.1] setting value
0: mm
-214748364.8 to 214748364.7 (m)
1: inch
-21474.83648 to 21474.83647 (inch)
2: degree
0 to 359.99999 (degree)
3: pulse
-2147483648 to 2147483647 (pulse)
(4) [Pr.14] Software stroke limit selection
Set whether to apply the software stroke limit on the "current feed value" or the "machine feed value". The
software stroke limit will be validated according to the set value.
(5) [Pr.15] Software stroke limit valid/invalid setting
Set whether to validate the software stroke limit during JOG/Inching operation and manual pulse generator
operation.
Value set with GX Works2 (unit)
0 to 6553.5 (m)
0 to 0.65535 (inch)
0 to 0.65535 (degree)
0 to 65535 (pulse)
Software stroke
limit lower limit
(Machine movement range)
OP
Value set with GX Works2 (unit)
CHAPTER 5 DATA USED FOR POSITIONING CONTROL
Value set with program (unit)
-1
m)
0 to 65535 (10
-5
0 to 65535 (10
inch)
-5
0 to 65535 (10
degree)
0 to 65535 (pulse)
Software stroke
limit upper limit
Emergency stop
limit switch
Value set with program (unit)
-2147483648 to 2147483647 (10
-2147483648 to 2147483647 (10
-5
0 to 35999999 (10
degree)
-2147483648 to 2147483647 (pulse)
*1
5
-1
m)
-5
inch)
127

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec-l ld75d

Table of Contents