15.5
List of Errors
The following table shows the error details and corrective actions to be taken when an error occurs.
Classification
Error
of errors
code
000
(Normal status)
001
Faults
Fatal errors
002
Internal circuit fault
PLC READY OFF during
101
operation
102
Drive unit READY OFF
Common
Test mode faults during
103
operation
650
Error name
Operation status at error occurrence
■Description
■Operation status at error occurrence
■Description
Hardware is faulty.
■Operation status at error occurrence
The system stops.
■Description
A PLC READY signal (Y0) is turned OFF during
operation.
■Operation status at error occurrence
The system stops with the setting (deceleration
stop/sudden stop) of the detailed parameter 2
Sudden stop selection (stop group 2). (Note that the
deceleration stop only occurs during the manual
pulse generator operation.)
■Description
The drive unit READY signal is turned OFF during
operation.
■Operation status at error occurrence
The system stops immediately.
■Description
The start of an operation is requested when the
drive unit READY signal is OFF.
■Operation status at error occurrence
The system does not start.
■Description
The personal computer cannot communicate with
the CPU module.
■Operation status at error occurrence
The system stops with the setting (deceleration
stop/sudden stop) of the detailed parameter 2
Sudden stop selection (stop group 2). (Note that the
deceleration stop only occurs during the manual
pulse generator operation.)
Action/Related buffer memory address/Set
range (Setting with program)
■Action
■Action
Check that there is no influence from noise.
■Action
Review the program which turns ON/OFF PLC
READY signal (Y0).
■Action
Check the power supply status of the drive unit,
wiring to the drive unit, and the connection status
of the connector.
■Action
• Check the power supply status of the drive unit,
wiring to the drive unit, and the connection
status of the connector.
• Check the values in [Pr.22] Input signal logic
selection.
• When a drive unit without READY signal output
is used, wire the system so that the drive unit
READY signal input of the LD75 is always ON.
■Action
• Check that there is no error on the personal
computer side I/F to which a cable is
connected.
• Because communication takes a long time
between the personal computer and a CPU
module, ensure high-speed communication by
setting the transmission speed to high at the
transfer setup of GX Configurator-QP or GX
Works2, or connecting the personal computer
directly to the communication I/F of the CPU
module.
• Reduce the load of communication by stopping
the access to a CPU module from GX
Developer or GX Works2 (such as monitor
function).